Hi guys
heating works fine but the burner goes in and out on hot water, the water never runs cold. From what i can see theres only the diverter and a microswitch on the hot water circuit. Which are working fine.
Is this somthing to do with the anti cycling?
Hello
I have a Vaillant Turbomax 824 boiler that has an issue where the boiler pressure is increasing slightly each time the hot water is used. I have pumped expansion vessel upto 12psi and ran it for a short while before I drained system again to add a radiator. When I checked the expansion...
Hi all, we went to a boiler where both central heating and dhw would turn on then off again. We then cleaned the plate heat exchanger thinking it would solve the problem but there was no change.
We then opened the combustion chamber. Please see attached pic. I take it the black marks and...
Hi all,
I was asked to attend a faulty boiler. Turbomax Plus 828e. When i arrived customer said boiler has been working fine then stopped. Customer said fault code showing was F60 and according to manual states 'electronic defect'. He switched the boiler off and back on and then there was noting...
I have a Vaillant VUW 242 Turbomax boiler with a timer, but when the clock is switched to timer position it does nothing. The boiler just runs continuously.
Not sure what to check
Thanks
James Tinker
Thread
boiler
check
not working
timer
turbomax
vaillant
working
The hot water from my 24kw Vailant Turbomax really seems to be struggling this winter - was fine in the summer. It's luke warm, even with the control up to max. Only way to get anything like hot water is to run the tap slowly. The ch flow pipes don't get hot. The heating is fine.
Any ideas...
Hi guys, a customer of mine has just moved house and they have a Vaillant Turbomax plus 824/828.
They keep needing to reset the boiler because of f22 code which says low system pressure.
I went round to have a look last week and the gauge said 0.3 bar so I tried to refill but the gauge was...
Hi All
I need to replace the diverter valve diaphragm on my Vaillant TURBOmax VUW 242E.
Does anybody know where I can get a service manual from to help.
Thanks
I hope I have posted this in the right place. Apologies if I havn't.
Has anyone had intermittant problems with hw on these. I went the other day and it was working fine on arrival. I told him to monitor it and ring me if it started again. I suspected the shower was faulty as the taps seemed...
Has anyone had intermittant problems with hw on these. I went the other day and it was working fine on arrival. I told him to monitor it and ring me if it started again. I suspected the shower was faulty as the taps seemed fine. I was thinking either Air pressure switch or Aqua Sensor, but to be...
so I have changed...
diverter valve
h/w heat exchanger
thermistor
aqua sensor
code coming up is s.54 flow gradient too steep
after speaking with vaillant suggesting that only other option Is pcb
ordered PCB for tomorrow
has anyone else had massive issue with these or just me?
Boiler...
drips.drops
Thread
changed
fast
hot
hot water
ideas
indent
plus
problems
rules
running
running out
turbomax
vaillant
water
Got intermittent fault on hot water with the above boiler. Microswitch been changed twice and weep line been cleared after being advised by technical. Made 3 sites visit and every time I'm on site the boiler fires no problem, original microswitch changed just over a week ago. Was working fine...
Gents, Pal rings me up this teatime, he's looked at a old Turbomax this afternoon that is going to be changed this summer anyway, his customer just wanted it to see the winter out, but its developed a fault
HW working ok /no probs
HTG works for around a 2/3 mins and knocks off, and just keeps...
Hi
Hi am having some trouble with a Vaillant turbomax vuw. I got called to look at it the client said it locks-out she resets it it ok for a while then locks out again.
I get there 1st thing I notice the is 0bar pressure. So I refilled it. Reset it fired up perfect 1st time. However, it...
hi, on a vaillant turbomax 242 or 282, does anybody no how much room you need to take the expansion vessel out from the top? as in, from the top of the boiler to the ceiling? also its sqaure and not round, hope someone can shed some light, thanks jon
I am having a problem with a friends boiler the heating is working fine but the hot water is running only warm if you reduce the flow at the tap the temperature increases but still not that hot. I have checked the flow and return are not heating up with the water running and the temperature...
Hi to all and I'm a new member in need of some advice. I have a problem with the DHW on Vaillant 828 boiler at a family friends house. When the hot tap is run the water runs warm for a while, then goes cold and the boiler shuts down although the DHW display showing the water is up to full...
Jay P
Thread
boiler
dhw
exchanger
plate
problem
turbomax
vaillant
water
I've been asked to do a gas cert on this property with this situation and the estate agent told me that another gas engineer had been out previously but was unhelpful. I went to have a quick look tonight so i could see what we are dealing with. the flue itself is 250mm away from the openable...
Hello guys, I've the same issue with turbomax plus in two different properties. Basically costumers left the boiler off while they been away for few days, they've come back , turned the boiler on and the boiler keeps blowing fuses on the PCB. Has anyone come across this before? Cheers